40 CFR §82.156 TABLE 1 · INTERACTIVE LOOKUP

EPA 608 Evacuation Requirements Cheat Sheet

Pick any appliance type, charge size, and recovery equipment manufacture date below to verify the exact EPA required vacuum level—then drill the evacuation questions below.

Interactive Required Vacuum Level Finder

Required EPA Vacuum 90% or 4 in. Hg Type I small appliance with operating compressor.

Complete 40 CFR §82.156 Table 1

Appliance Type EPA Type Charge Before Nov 15, 1993 On/After Nov 15, 1993 Exam Note
Small Appliances (Operating Compressor) Type I ≤ 5 lbs (factory sealed) 80% or 4 in. Hg 90% or 4 in. Hg Reaching 4 in. Hg vacuum always satisfies Type I recovery.
Small Appliances (Non-Operating Compressor) Type I ≤ 5 lbs (factory sealed) 80% or 4 in. Hg 80% or 4 in. Hg Access both high & low sides if capillary/drier restriction exists.
HCFC-22 (R-22) Appliances Type II < 200 lbs 0 in. Hg 0 in. Hg Applies to residential/light commercial R-22 split systems & RTUs.
HCFC-22 (R-22) Appliances Type II ≥ 200 lbs 4 in. Hg 10 in. Hg Isolated component for non-major repair may evacuate to 0 psig.
Other High-Pressure (R-410A, R-134a, R-404A, R-407C) Type II < 200 lbs 4 in. Hg 10 in. Hg Verify recovery tank is rated 400 psig for R-410A / R-32 / R-454B.
Other High-Pressure (R-410A, R-134a, R-404A, R-407C) Type II ≥ 200 lbs 4 in. Hg 15 in. Hg Deepest Type II recovery vacuum requirement.
Very High-Pressure (R-13, R-503) Type II Any size 0 in. Hg 0 in. Hg Boiling point below -50°C at atmospheric pressure.
Low-Pressure Centrifugal Chillers (R-11, R-123, R-514A) Type III Any size 25 in. Hg 25 mm Hg absolute 25 mm Hg abs ≈ 29 in. Hg vacuum (25,000 microns). Circulate or drain water to prevent freezing!
EVAC-DRILL 18 Questions · 72% Pass Line

Evacuation & Vacuum Standards Focused Drill

Q 1 / 18 Loading topic…
Score: 0/0

Which gas is approved and safe for pressurizing an HVACR system during a standing pressure leak test?

EPA 608 Evacuation FAQ

Why does EPA 608 distinguish between recovery equipment manufactured before vs. on/after November 15, 1993?

November 15, 1993 was the effective date when EPA implemented stricter certification standards for newly manufactured refrigerant recovery equipment. Grandfathered pre-1993 machines were allowed slightly shallower vacuum levels (e.g., 4 in. Hg instead of 10 or 15 in. Hg on high-pressure appliances, and 25 in. Hg instead of 25 mm Hg absolute on chillers).

What is the exception when an appliance is leaking so badly it cannot reach the required EPA vacuum?

Under 40 CFR §82.156(a)(2), if leaks in an appliance make evacuation to the standard vacuum level unattainable (or would pull excessive air into the recovery cylinder), technicians must evacuate to the lowest attainable level—typically atmospheric pressure (0 psig)—before opening to repair the leak.