Interactive Refrigerant Pressure-Temperature (P/T) Chart
Slide the temperature control to compare saturated gauge pressures across R-410A, R-22, R-32, R-454B, R-134a, R-404A, R-407C, R-123, R-290, and R-600a—plus ODP, GWP, oil type, and ASHRAE 34 safety class.
Complete Refrigerant Properties, ODP, GWP & Saturation Table
| Code | Class / Safety | ODP / GWP | Boiling Pt | 32°F | 40°F | 75°F | 100°F | Oil / Notes |
|---|---|---|---|---|---|---|---|---|
| R-410A | HFC / A1 | 0 / 2088 | -61°F | 101.6 psig | 118.9 psig | 218.2 psig | 316.9 psig | POE — <0.2°F (near-azeotropic) |
| R-22 | HCFC / A1 | 0.055 / 1810 | -41.4°F | 57.7 psig | 68.5 psig | 132.2 psig | 195.9 psig | Mineral / AB — 0°F (single component) |
| R-32 | HFC / A2L | 0 / 675 | -61°F | 106.9 psig | 124.8 psig | 227.5 psig | 329.0 psig | POE — 0°F (single component) |
| R-454B | HFO/Blend / A2L | 0 / 466 | -59.6°F | 94.6 psig | 111.0 psig | 204.8 psig | 298.1 psig | POE — ~2.7°F (zeotropic) |
| R-134a | HFC / A1 | 0 / 1430 | -15°F | 27.8 psig | 35.0 psig | 78.7 psig | 124.2 psig | POE / PAG — 0°F (single component) |
| R-404A | HFC / A1 | 0 / 3922 | -51.7°F | 73.1 psig | 85.9 psig | 159.0 psig | 232.0 psig | POE — ~0.9°F (near-azeotropic) |
| R-407C | HFC / A1 | 0 / 1774 | -46.5°F | 56.9 psig | 68.1 psig | 134.8 psig | 203.0 psig | POE — ~9–12°F (high glide) |
| R-123 | HCFC / B1 | 0.02 / 77 | 82.1°F | 22.2" Hg | 20.1" Hg | 4.4" Hg | 7.4 psig | Mineral / AB — 0°F (single component) |
| R-290 | HC / A3 | 0 / 3 | -43.8°F | 53.9 psig | 63.8 psig | 120.7 psig | 177.5 psig | POE / Mineral — 0°F (single component) |
| R-600a | HC / A3 | 0 / 3 | 10.9°F | 8.6 psig | 12.5 psig | 36.5 psig | 62.1 psig | Mineral / AB — 0°F (single component) |
Refrigerant P/T Chart FAQ
How do technicians use a Pressure-Temperature (P/T) chart on the EPA 608 exam?
A P/T chart lets you identify a pure refrigerant in a stabilized cylinder, detect non-condensable air (pressure higher than chart saturation at ambient temp), determine if a low-pressure chiller is cold enough to freeze evaporator water (below 32°F saturation), and calculate evaporator superheat and condenser subcooling.
Why are R-123 pressures shown as negative numbers (in. Hg vacuum) below 80°F?
HCFC-123 has an atmospheric boiling point of 82.1°F. At normal room and chilled-water temperatures (32°F–75°F), R-123 sits below 0 psig—meaning it operates in a vacuum measured in inches of mercury (in. Hg).
How do R-32 and R-454B pressures compare to R-410A?
Both A2L replacements operate in the same high-pressure class as R-410A: R-32 runs roughly 5% higher pressure than R-410A (227.5 psig vs 218.2 psig at 75°F), while R-454B runs roughly 6% lower (204.8 psig at 75°F) with a small ~2.7°F glide.