EPA 608 Type II Practice Test (High-Pressure Appliances)
The most widely used HVACR certification module. Practice 35 high-pressure questions covering evacuation levels (0 / 10 / 15 in. Hg), 10%/20%/30% leak thresholds, push-pull liquid recovery, pump-down safety, R-410A 400 psig tanks, and A2L (R-32 / R-454B) transitions.
EPA 608 Type II Practice Exam (25Q Simulation · 35-Q Pool)
How does the EPA define a "high-pressure" refrigerant covered under Type II certification?
0% (0 / 0)
Question-by-Question Review
Type II Critical Field & Exam Rules
1. Evacuation Matrix (Post-11/15/1993)
- HCFC-22 < 200 lbs: 0 in. Hg
- HCFC-22 ≥ 200 lbs: 10 in. Hg
- Other High-Pressure < 200 lbs: 10 in. Hg
- Other High-Pressure ≥ 200 lbs: 15 in. Hg
- Major repair = compressor, condenser, evaporator, or auxiliary heat exchanger coil.
2. Compressor & Cylinder Safety
- Never run a hermetic compressor under vacuum — motor winding arc-over destroys it.
- R-410A / R-32 / R-454B cylinders require 400 psig DOT service rating (4BA400/4BW400).
- A2L tanks (R-32, R-454B) use left-hand valve threads and a red shoulder band.
- Push-pull liquid recovery speeds up systems >15 lbs with a receiver.
EPA 608 Type II FAQ
What appliances require EPA 608 Type II certification?
High-pressure and very high-pressure stationary equipment except small appliances—including residential split-system AC and heat pumps, commercial rooftop units (RTUs), supermarket refrigeration racks, walk-in coolers/freezers, and commercial ice machines using R-22, R-410A, R-134a, R-404A, R-32, or R-454B.
What are the exact Type II evacuation levels I need to memorize?
For equipment built on/after Nov 15, 1993: HCFC-22 <200 lbs = 0 in. Hg; HCFC-22 ≥200 lbs = 10 in. Hg; Other High-Pressure (R-410A, R-134a, R-404A, R-407C) <200 lbs = 10 in. Hg; Other High-Pressure ≥200 lbs = 15 in. Hg; Very High-Pressure (R-13, R-503) = 0 in. Hg.
What are the current EPA Type II leak repair rate triggers for systems ≥50 lbs?
10% per year for comfort cooling, 20% per year for commercial refrigeration, and 30% per year for industrial process refrigeration (IPR). Leaks must be repaired within 30 days with initial and 10-day follow-up verification tests.