EPA 608 Type III Practice Test (Low-Pressure Chillers)
Conquer the trickiest section of the Universal exam. Practice 30 Type III questions covering R-11/R-123/R-1233zd(E) centrifugal chillers, 25 mm Hg absolute evacuation, 10 psig max leak-test pressure, 15 psig rupture discs, purge units, and ASHRAE 15 B1 safety.
EPA 608 Type III Practice Exam (25Q Simulation · 30-Q Pool)
How does the EPA define a "low-pressure" refrigerant covered under Type III certification?
0% (0 / 0)
Question-by-Question Review
The 6 Must-Know Type III Chiller Numbers
Equals ~29 in. Hg vacuum (25,000 microns). Pre-Nov 15, 1993 equipment = 25 in. Hg.
Never exceed 10 psig with dry nitrogen or controlled hot water—rupture disc bursts at 15 psig.
Building chillers ≥50 lbs must be repaired within 30 days if annual leak rate exceeds 10%.
Higher toxicity, non-flammable; requires ASHRAE 15 room vapor detector & exhaust fan.
Warm compressor oil before draining so dissolved R-123 boils out for recovery.
Recover liquid then vapor; when RECHARGING from vacuum, charge VAPOR first to prevent tube freeze!
EPA 608 Type III FAQ
Why do most residential HVAC technicians struggle most with EPA 608 Type III?
Type III covers low-pressure centrifugal chillers (R-11, R-123, R-514A, R-1233zd) that operate in a vacuum—the exact opposite of positive-pressure residential AC systems. Once you memorize 5 core chiller numbers (25 mm Hg abs, 10 psig max test, 15 psig rupture disc, 130°F oil warm-up, vapor-first charging), Type III becomes very predictable.
Why must you charge vapor first into an evacuated R-123 chiller?
Pouring liquid R-123 into a deep vacuum causes rapid flash-boiling well below 32°F, freezing water inside the evaporator tubes and splitting the copper tubes. Charge vapor first (with water pumps running) until pressure exceeds freezing saturation (~20 in. Hg vac / 0 psig) before adding liquid.
Where does the chiller purge unit draw suction from?
From the top of the condenser, where non-condensable air accumulates. High-efficiency purge units condense out the refrigerant vapor, return liquid refrigerant to the evaporator, and vent less than 0.1 lb of refrigerant per pound of air purged.