EPA 608 Study Guide & Printable Cheat Sheet (2026)
Every high-yield date, vacuum number, leak threshold, and safety rule tested on Core, Type I, Type II, and Type III—formatted for instant browser reading or crisp black-and-white printing.
1. Core Essentials (Mandatory)
- Stratospheric Ozone: 10–30 mi altitude; shields UV-B; 1 Cl atom destroys up to 100,000 O3 molecules.
- ODP vs GWP: CFCs (highest ODP, phased out Jan 1, 1996) > HCFCs (R-22 virgin banned Jan 1, 2020) > HFCs/HFOs/HCs (0 ODP; HFCs have high GWP → AIM Act 85% phasedown by 2036).
- Venting Ban: ODS banned July 1, 1992; Substitutes banned Nov 15, 1995. De minimis releases & approved natural/HC refrigerants (R-290, R-600a, CO2, NH3) exempt.
- Penalties: Civil fines >$44,539+/day (inflation-adjusted); whistleblower award up to $10,000; cert loss.
- 3 Rs: Recover (remove), Recycle (clean for same owner), Reclaim (virgin AHRI 700 purity; required before resale).
- Cylinders: DOT 4BA/4BW; gray body / yellow top; max 80% liquid fill; 5-yr hydrostatic test; never refill DOT-39.
- Safety: Pressure test ONLY with dry nitrogen + regulator; never oxygen/air. Blends (400-series) charge as liquid.
2. Type I — Small Appliances (≤ 5 lbs)
- Definition: Factory-manufactured, factory-charged, hermetically sealed with ≤ 5 lbs (excludes MVACs = §609).
- Post-11/15/1993 Recovery: 90% if compressor works, 80% if inoperative, or 4 in. Hg vacuum. Pre-1993 = 80% either way.
- Passive (System-Dependent) Limit: Prohibited on appliances with > 15 lbs. Tap both high & low sides if restricted/inoperative.
- Piercing Valves: Temporary only—rubber gaskets leak over time.
- Hydrocarbons (R-600a / R-290): ASHRAE A3 (flammable); red tube markings (PMS #185); ≤150g domestic fridge limit; do NOT use A1 spark-prone recovery machines.
- Disposal: Final disposer (scrap yard) must recover or keep signed recovery statement for 3 years.
3. Type II — High-Pressure Systems
- Boiling Point: Between -50°C and 10°C (R-22, R-410A, R-134a, R-404A, R-407C, R-32, R-454B).
- Evacuation (Post-1993): R-22 <200 lbs = 0 in. Hg; R-22 ≥200 lbs = 10 in. Hg; Other HP <200 lbs = 10 in. Hg; Other HP ≥200 lbs = 15 in. Hg; Very HP (R-13/R-503) = 0 in. Hg.
- Major Repair: Removing compressor, condenser, evaporator, or auxiliary heat exchanger coil.
- Leak Repair (≥50 lbs): Comfort cooling 10%, Commercial refrig 20%, IPR 30%. Repair within 30 days; initial + 10-day follow-up verification. ≥125%/yr = chronic leaker EPA report due March 1.
- Field Rules: Recover liquid first (push-pull on >15 lb systems w/ receiver); NEVER run hermetic compressor under vacuum; R-410A tanks rated 400 psig; A2L cylinders have left-hand threads + red band.
4. Type III — Low-Pressure Chillers
- Boiling Point: Above 10°C (50°F) — operates in a vacuum (R-11, R-123, R-514A, R-1233zd(E)).
- Evacuation: Post-Nov 15, 1993 = 25 mm Hg absolute (~29 in. Hg vac / 25,000 microns). Pre-1993 = 25 in. Hg.
- Leak Testing: Max 10 psig (dry N2 or controlled hot water) because rupture disc bursts at 15 psig (vented outdoors per ASHRAE 15).
- Purge Unit: Pulls non-condensable air from top of condenser; excessive purge runtime = active air leak!
- Freeze Prevention: Circulate or drain chilled/condenser water during recovery/evacuation; recharge VAPOR first until saturation >32°F before adding liquid through evaporator charging valve.
- Oil & Safety: Warm oil to ~130°F before draining; R-123 is B1 (higher toxicity, OEL 50 ppm, requires room vapor monitor + exhaust).
Master Evacuation & Leak Threshold Tables
| Appliance Category | Charge | Pre-11/15/93 | Post-11/15/93 |
|---|---|---|---|
| Small Appliances (Operating Compressor) | ≤ 5 lbs (factory sealed) | 80% or 4 in. Hg | 90% or 4 in. Hg |
| Small Appliances (Non-Operating Compressor) | ≤ 5 lbs (factory sealed) | 80% or 4 in. Hg | 80% or 4 in. Hg |
| HCFC-22 (R-22) Appliances | < 200 lbs | 0 in. Hg | 0 in. Hg |
| HCFC-22 (R-22) Appliances | ≥ 200 lbs | 4 in. Hg | 10 in. Hg |
| Other High-Pressure (R-410A, R-134a, R-404A, R-407C) | < 200 lbs | 4 in. Hg | 10 in. Hg |
| Other High-Pressure (R-410A, R-134a, R-404A, R-407C) | ≥ 200 lbs | 4 in. Hg | 15 in. Hg |
| Very High-Pressure (R-13, R-503) | Any size | 0 in. Hg | 0 in. Hg |
| Low-Pressure Centrifugal Chillers (R-11, R-123, R-514A) | Any size | 25 in. Hg | 25 mm Hg absolute |
| Leak Repair Sector (≥50 lbs) | Annual Trigger | Repair Window | Verification |
|---|---|---|---|
| Comfort Cooling | 10% | 30 days | Initial (before recharge) + Follow-up within 10 days |
| Commercial Refrigeration | 20% | 30 days | Initial (before recharge) + Follow-up within 10 days |
| Industrial Process Refrigeration (IPR) | 30% | 30 days (120 days if industrial shutdown required) | Initial + Follow-up within 10 days |
| Chronically Leaking Appliance Report | ≥ 125% / calendar year | EPA report due March 1 of following year | Documented repair / retrofit / retirement actions |
EPA 608 Study Guide FAQ
Can I print this EPA 608 study guide as a clean 1-to-2 page cheat sheet?
Yes. Click "Print 1-Page Cheat Sheet" above—our print stylesheet strips out site navigation, buttons, and backgrounds automatically so you get crisp black-and-white technical tables ready for your study binder or truck clipboard.
How long does it take to study for the EPA 608 Universal exam?
Most HVAC apprentices and working techs pass Universal in 5 to 10 hours of focused study: 2 hours reviewing this Core + Type I/II/III sheet, followed by scoring 85%+ across all four module practice tests and clearing their Wrong-Answer Notebook.